--- title: 事件推送 editLink: false --- # 事件推送 事件推送功能,由设备端EMS触发,向客户APP进行消息推送的功能。主要用于在某些事件节点上给用户一个提示,以便知晓设备的功能执行情况及一些处理措施。 事件推送表(中文): | ID | 标题 | 内容 | | :-: | :-: | ---- | | 1 | 市电停电 | 电网中断了。FHP已经存储了$1kWh,根据过去72小时的最高消耗,大约可以提供$2的备电时长。 | | 2 | 市电恢复 | 已恢复至并网工作。 | | 3 | 电量低 | FHP电量低 。 | | 4 | 电量极低 | FHP电量极低,该设备即将进入休眠状态。 | | 5 | 黑启动失败 | FHP系统黑启动失败。 | | 6 | EPO停机 | 由于EPO动作,家庭供电被切断。 | | 7 | EPO复位 | EPO复位,家庭供电恢复。 | | 8 | 发电机接入 | 发电机正常运行,并已接入FHP系统。 | | 9 | 发电机退出 | 发电机退出FHP系统。 | | 10 | 紧急备电开始 | aGate已收到风暴通知,正在以紧急备用模式为电池充电。 | | 11 | 紧急备电结束 | 风暴信息变更,aGate将退出风暴模式,恢复先前的工作模式。 | | 12 | 固件升级开始 | FHP系统开始升级。 | | 13 | 固件升级结束 | FHP系统升级完成。 | | 14 | 系统停止 | FHP进行系统保护。 | | 15 | aPower停止 | aPower设备发生故障。 | | 16 | 离网过载 | 由于过载导致系统暂时保护。 | | 17 | 智能负载断开 | FHP系统电量低于限值,已断开智能负载。 | | 18 | 智能负载断开 | FHP系统电量低于限值,已断开智能负载。 | | 19 | 智能负载低SOC切断恢复 | | | 20 | 离网超发断光伏 | | | 21 | 离网恢复光伏 | | | 22 | 启动发电机 | | | 23 | 停止发电机 | | | 24 | 发电机启动异常 | 由于\{0\},导致发电机启动异常 | | 25 | 发电机运行异常 | 发电机运行异常,发电机将被关闭。 | | 26 | 系统休眠 | FHP系统电量耗尽,进入长时休眠状态。 | | 27 | 离网过载预警 | 负载功率超过FHP系统额定功率,即将触发系统保护。 | | 28 | 光伏接入尝试 | 发电机输出不稳定,无法对电池充电。系统正在尝试接入光伏充电。 | | 29 | 黑启动尝试 | 系统正在进行黑启动尝试。 | | 30 | 离网过载锁定 | 频繁触发系统过载保护,系统锁定。 | | 31 | 系统电量恢复 | 系统电量已经恢复至20%。 | | 32 | 智能线路已充满 | 智能线路已充满,退出定量充电。 | | 33 | 发电机演习成功 | 发电机演习成功 | | 34 | 发电机演习失败 | 发电机演习失败,可能是由于启动超时或其他异常情况 | | 35 | 发电机工作不稳定 | 发电机工作不稳定,aPower可能会进入待机模式 | | 36 | 发电机恢复稳定 | 发电机恢复稳定工作状态 | | 37 | 进入休眠模式 | 电池设备因线路异常进入休眠状态,请恢复线路后再试 | | 38 | V2L接入 | 系统已经接入V2L紧急电源模式,现在已经可以使用您的电动汽车为系统提供供载。请您注意降低家庭负载消耗功率。 | | 39 | V2L退出 | 电动汽车供载结束,系统已经退出V2L紧急电源模式。 | | 40 | 紧急备电模式退出 | 备电结束,aGate已切换至\{0\}模式。 | | 41 | V2L输出过载保护告警 | 您正在使用V2L模式。目前您的电动汽车输出功率已达到额定功率的 80%,请注意负载消耗情况。 | | 42 | V2L输出过载切断 | 您正在使用V2L模式。您的电动汽车输出功率已超过额定功率,V2L线路已切断。 | | 43 | PCS保护限制光伏 | 主电池板工作电流超过设定值的95%,需要限制光伏。 | | 44 | PCS保护切断智能负载 | 主电池板工作电流超过设定值的 100%,$1已被切断。 | | 45 | V2L启动异常 | 由于\{0\},导致V2L启动异常 | | 46 | - | - | | 47 | - | - | | 48 | PCS保护调节电池功率 | 主电池板工作电流超过设定值的 90%,需要调节电池功率。 | | 49 | 退出PCS保护调节电池 | 主面板工作电流降低到设定值的 85%,退出电池功率调节。 | | 50 | 退出PCS保护,恢复光伏 | 主面板工作电流降低到设定值的 85%,恢复光伏。 | | 51 | 退出PCS保护,恢复智能负载 | 由于主面板工作电流降至设定值的 80%,$1已恢复。 | | 1401 | 系统暂停 | FHP暂时保护,请等待系统尝试恢复。 | | 1402 | 系统停止 | FHP进行系统保护。 | | 1403 | 系统异常 | 系统检测异常。 | 事件推送表(英文): | ID | Title | Content | | :-: | :-: | ---- | | 1 | Grid Outage | There is a grid outage. aGate has stored $1kWh for an estimated $2 of backup based on the highest consumption in the past 72h. | | 2 | Grid restored | Grid power has been restored. | | 3 | Low SOC | aGate battery storage is at SOC lower limit. | | 4 | Extremely low SOC | The aGate will enter sleep mode as the stored energy is almost depleted. | | 5 | Black start failure | The aGate failed to black start. | | 6 | EPO downtime | The home is powered off due to EPO activation. | | 7 | EPO replaced | The EPO has been reset your home is powered. | | 8 | Generator access | The generator is connected and supplying the home. | | 9 | Generator exit | Generator has been turned off. | | 10 | Emergency backup start | The aGate has received a storm notification and is charging the battery in emergency backup mode. | | 11 | Emergency backup end | Storm information has changed. The aGate will be out of storm mode, and resume the previous operating mode. | | 12 | Firmware upgrade | Your aGate is upgrading. | | 13 | Firmware upgrade completed | Your aGate upgrade is completed. | | 14 | aGate shutdown | Your aGate shut down for self-protection. | | 15 | aPower failure | There is an aPower malfunction. | | 16 | System overloading | Your aGate temporarily shut down due to an overload. | | 17 | Smart Circuits disconnected | The Smart Circuits have been disconnected as the battery SOC battery is below the set threshold. | | 18 | Smart Circuits disconnected | The Smart Circuits have been disconnected as the battery SOC battery is below the set threshold. | | 19 | Smart circuit reconnected | | | 20 | Solar disconnected | | | 21 | Solar reconnected | | | 22 | Generator start | | | 23 | Generator stop | | | 24 | Generator start abnormality | Generator start abnormality due to \{0\}. | | 25 | Generator abnormality | Your aGate is powered off due to battery depletion. | | 26 | System power-off | Your aGate is powered off due to battery depletion. | | 27 | Off-grid overload warning | Your aGate over-protection is about to be triggered, as your loads are overloading the battery. | | 28 | Solar attempt | The generator output is unstable and cannot recharge the battery. The aGate is attempting to charge the battery from solar. | | 29 | Black startup attempt | Your aGate is attempting a black start. | | 30 | aGate shutdown due to overload | The aGate shut down due to frequent overload protection. | | 31 | Battery power recovery | FHP battery has been recharged to SOC 20%. | | 32 | The load on the smart circuit is fully charged | The load on the smart circuit is full, the quantitative charging will end. | | 33 | Generator exercise success | Generator exercise success. | | 34 | Generator exercise fail | Generator exercise fail, possibly due to startup timeout or other abnormal conditions. | | 35 | Generator instability | The generator is unstable and the aPower(s) may enter standby mode. | | 36 | Generator stabilization | The generator returned to stable operation. | | 37 | Enter hibernation mode | The battery device went into hibernation mode due to a circuit abnormality. Please restore the circuit and try again. | | 38 | V2L mode access | V2L emergency power mode is enabled, and your EV is ready to power home loads. You might need to reduce in-essential home loads. | | 39 | V2L mode exit | Your EV has stopped powering loads, V2L emergency power mode is turned off. | | 40 | Emergency backup over. The aGate has been switched to the XXX(Previous mode) mode. | Emergency backup over. The aGate has been switched to the XXX(Previous mode) mode. | | 41 | V2L output overload protection alarm | You are using V2L mode. Currently the output power of your electric vehicle has reached 80% of the rated power, please pay attention to the load consumption. | | 42 | V2L output overload cut off | You are using V2L mode. The output of your electric vehicle exceeds the rated power. The V2L line has been disconnected. | | 43 | PCS protection to limit solar | Main panel operating current exceeds 95% of the set value, requires limiting the solar. | | 44 | PCS protection to shed smart circuits | Your house is using too much power and is nearing the safe limit of operation. $1 of your Smart Circuit is being temporarily disconnected until the home load decreases. | | 45 | V2L start abnormality | V2L start abnormality due to \{0\}. | | 46 | - | - | | 47 | - | - | | 48 | PCS protection to regulate battery power | Your house is using too much power and is nearing the safe limit of operation. Regulating the battery power until the home load decreases. | | 49 | Exit PCS protection to regulate battery power | Main panel operating current is reduced to 85% of the set value, exiting battery power regulation. | | 50 | Exit PCS protection, restore solar | Main panel operating current is reduced to 85% of the set value, restore solar. | | 51 | Exit PCS protection, restore smart circuits | Power to the $1 of Smart Circuit has been restored. Your home load has reduced to safe limits. | | 1401 | aGate suspension | Your aGate temporarily stopped working, and it will restart automatically. | | 1402 | aGate shutdown | The aGate detected an abnormality. | | 1403 | aGate abnormality | The aGate detected an abnormality. | ## No.1 市电停电(Grid Outage) FWH系统从并网运行模式切换到离网运行模式,市电停电或市电质量不满足可正常使用标准。 ## No.2 市电恢复(Grid restored) 市电恢复正常,FWH系统由离网运行模式切换到并网运行模式,系统接入市电。 ## No.3 电量低(Low SOC) FWH系统电量低于10%,提醒用户注意电量使用情况。 ## No.4 电量极低(Extremely low SOC) FWH系统电量为0%,系统即将关机。 等待市电来电或黑启动尝试(每天10:00/12:00/14:00) :::warn aPower预留了5%的SOC用于黑启动尝试,黑启动尝试时电量可能会被负载消耗掉,导致黑启动尝试失败或者尝试次数锐减。请断开家中所有负载,以便提高黑启动成功率,避免电池完全耗尽。 当电池完全耗尽时,将无法进行黑启动尝试,只能使用市电或油机给系统补电。 当电池完全耗尽后,电芯一般只能维持大概15天左右,维护人员需在这个期限内及时补电,否则将会给电池带来不可逆的损伤。 ::: ## No.5 黑启动失败(Black start failure) 代码中已经屏蔽此事件,不会推送。 ## No.6 EPO停机(EPO downtime) EPO按钮被按下,系统进入紧急停机状态。 ## No.7 EPO复位(EPO replaced) EPO按钮复位,系统将重新初始化并尝试开机。 ## No.8 发电机接入(Generator access) 发电机已经正常接入FWH系统,供载或充电。 ## No.9 发电机退出(Generator exit) 发电机断开与FWH系统的连接。 - 演习完成退出 - 油机启动超时退出(油机未正常启动或油机启动超时时间设置过短) - 油机故障退出([发电机快检异常](./AlarmTable.md#301a-发电机快检异常)、[发电机锁相失败](./AlarmTable.md#301b-发电机锁相失败)、[发电机输出不稳](./AlarmTable.md#301c-发电机输出不稳)、[发电机故障退出](./AlarmTable.md#3020-发电机故障退出)) ## No.10 紧急备电开始(Emergency backup start) 进入紧急备电状态,系统将开始使用电网充电,并将电池充至100%,为极端天气情况提供电力支持。 ## No.11 紧急备电结束(Emergency backup end) 极端天气已结束,紧急备电状态解除,系统恢复到正常运行模式。 ## No.12 固件升级开始(Firmware upgrade) 接收到云端固件升级请求,开始升级设备固件。 ## No.13 固件升级结束(Firmware upgrade completed) 固件升级流程结束,升级结果可在Fleetview中查看。 ## No.14 系统停止(aGate shutdown) 系统停止运行,有以下几种可能性: - EPO被按下 - NewHome站点 - 所有aPower开关被置于off状态或处于故障状态无法开机 - 系统升级中 ## No.15 aPower停止(aPower failure) 有一台或多台aPower处于非正常运行状态,可能原因: - 有一台或多台aPower开关被置于off状态 - 有一台或多台aPower进入故障状态导致关机 - 系统升级,关闭aPower - 油机运行不稳定,关闭aPower ## No.16 离网过载(System overloading) 离网运行模式下,系统长时间超出额定功率放电供载,说明此时系统负荷过大,需降低家庭负载。 此时可能会伴随着以下故障: - [BMS-SOP限功率保护](./AlarmTable.md#4x68-bms-sop限功率保护) - [逆变过载保护](./AlarmTable.md#4x07-逆变过载保护) ## No.17 智能负载断开(Smart Circuits disconnected) 当开启智能负载的SOC阈值(SOC Threshold)功能时,离网系统的SOC低于此阈值后会断开智能负载并推送此消息。 ## No.18 智能负载断开(Smart Circuits disconnected) 此消息未使用,与No.17重复。 ## No.19 智能负载低SOC切断恢复(Smart circuit reconnected) 此消息未使用。 ## No.20 离网超发断光伏(Solar disconnected) 触发[光伏继电器异常断开](./AlarmTable.md#3023-光伏继电器异常断开)故障后,推送此消息。 此消息通常还会伴随着以下故障同时出现: - xxxxx - xxxxx ## No.21 离网恢复光伏(Solar reconnected) [光伏继电器异常断开](./AlarmTable.md#3023-光伏继电器异常断开)故障消息后,推送此消息。 ## No.22 启动发电机(Generator start) 满足发电机启动条件,尝试启动并接入发电机。 发电机启动条件如下: - 发电机演习 - 到达用户设定的发电机充电启动时间 - 系统SOC低于用户设定的发电机启动SOC - 用户使用APP操作手动启动发电机 ## No.23 停止发电机(Generator stop) 满足发电机停止条件,尝试停止发电机并端口发电机继电器。 发电机停止条件如下: - 发电机启动超时,在设定的发电机启动时间内,发电机无法启动或保持稳定运行(同时会伴随No.24事件) - 演习完成退出 - 到达用户设定的发电机充电结束时间 - 系统SOC高于用户设定的发电机停止SOC - 用户使用APP操作手动停止发电机 - 光伏尝试(同时会推送No.28事件) ## No.24 发电机启动异常(Generator start abnormality) 发电机启动超时,触发此事件。 ## No.25 发电机运行异常(Generator abnormality) [发电机故障退出](./AlarmTable.md#3020-发电机故障退出)告警出现时,会触发此推送。 ## No.26 系统休眠(System power-off) 进入系统休眠时,推送此事件。 休眠共有以下几种情况: - NewHome休眠,休眠设定时间30天 - 黑启动失败休眠,休眠至下次黑启动时间 - 所有aPower SOC下降至0.5%,深度休眠,休眠设定时间30天 ## No.27 离网过载预警(Off-grid overload warning) 当有某台或多台aPower报出[输出过载告警](./AlarmTable.md#4x14-输出过载告警)时,触发此推送。 ## No.28 光伏接入尝试(Solar attempt) 发电机运行过程中,如果处于中午可能太阳较大的时间点(10点、12点、14点),发电机会尝试退出,并接入光伏,尝试使用光伏充电,此时会推送此事件。 ## No.29 黑启动尝试(Black startup attempt) 在系统SOC低于0%而导致的休眠后,当到达黑启动尝试时间点(10点、12点、14点)时,系统将开机,接入光伏,尝试黑启动。此时将会推送此事件。 :::warn 此时应提示用户减载,避免因负载导致快速耗尽电池电量,导致系统长期休眠,无法充电。 电池耗尽后,需及时补电,否则可能对电池照成不可逆的伤害。 ::: ## No.30 离网过载锁定(aGate shutdown due to overload) 系统连续输出过载导致触发告警:[输出过载20次锁定](./AlarmTable.md#4x1c-输出过载20次锁定) 提示用户家中负载过重或电器出现短路现象。 ## No.31 系统电量恢复(Battery power recovery) 系统电量恢复消息,提示用户系统已退出低电量状态(系统SOC高于20%)。 ## No.32 智能线路已充满(The load on the smart circuit is fully charged) 暂未实现。。。 ## No.33 发电机演习成功(Generator exercise success) 油机演习完成消息推送。 ## No.34 发电机演习失败(Generator exercise fail) 油机演习失败消息推送。常伴随着油机故障出现。 以下情况会出现油机演习失败: - 演习中触发EPO按钮 ## No.35 发电机工作不稳定(Generator instability) ## No.36 发电机恢复稳定(Generator stabilization) ## No.37 进入休眠模式(Enter hibernation mode) ## No.38 V2L接入(V2L mode access) ## No.39 V2L退出(V2L mode exit) ## No.40 紧急备电模式退出(Emergency backup over. The aGate has been switched to the XXX(Previous mode) mode.) ## No.41 V2L输出过载保护告警(V2L output overload protection alarm) ## No.42 V2L输出过载切断(V2L output overload cut off) ## No.43 PCS保护限制光伏(PCS protection to limit solar) ## No.44 PCS保护切断智能负载(PCS protection to shed smart circuits) ## No.45 V2L启动异常(V2L start abnormality) ## No.46 *预留 ## No.47 *预留 ## No.48 PCS保护调节电池功率(PCS protection to regulate battery power) ## No.49 退出PCS保护调节电池(Exit PCS protection to regulate battery power) ## No.50 退出PCS保护,恢复光伏(Exit PCS protection, restore solar) ## No.51 退出PCS保护,恢复智能负载(Exit PCS protection, restore smart circuits) ## No.1401 系统暂停(aGate suspension) ## No.1402 系统停止(aGate shutdown) ## No.1403 系统异常(aGate abnormality)